HTST Valve Schedule |
||
|
Valve # |
Valve Type |
Function |
|
28 |
MID actuator |
CLT1 inlet |
|
29 |
MID actuator |
Open during CIP cleaning; closed during forward flow so all product goes through regenerative heating system; mid-position during start-up to allow some milk to pass through regenerative heating system. |
|
30 |
|
spare valve |
|
31 |
valve positioner |
Serves as a flow control device based on output from MM1. When flow is diverted, it partially closes to induce a pressure loss approximately equal to that found in the mechanical components of the system located after the flow diversion valves. Open when processing mix or milk. |
|
32 |
actuator |
extended hold tube inlet for ice cream mix |
|
33 |
actuator |
extended hold tube outlet for ice cream mix |
|
34 |
flow diversion |
divert valve |
|
35 |
flow diversion |
leak detect |
|
36 |
valve positioner |
Used to by-pass regenerative heating by-pass to keep (cheese) milk warm. Open for cheese milk and yogurt; closed for mix |
|
37 |
|
spare valve |
|
38 |
MID actuator |
Directs product to separator when open; product by-passes separator when closed; mid position used for CIP operation. |
|
39 |
throttling valve |
controls skim milk back pressure from PS5 signal |
|
40 |
MID actuator |
skim milk shutoff |
|
41 |
throttling valve |
controls regen back pressure from PS3 signal |
|
42 |
MID actuator |
HTST1 to pasteurized tanks PT1 and PT2) |
|
43 |
MID actuator |
HTST1 to cheese vats |
|
44 |
MID actuator |
HTST1 to skim tank (SK1) |
|
45 |
MID actuator |
HTST1 to recycle. Serves as a safety valve that opens if a set pressure limit is exceeded (fails open) |
|
46 |
MID actuator |
HTST1 to drain |
|
MSV 1 |
sampling valve |
sampling valve for cream stream |
|
MSV 2 |
sampling valve |
sampling valve for skim stream |