> Extension & Outreach
>Electrical Publications
STANDBY POWER SYSTEMS
Agricultural Engineering Department
Michigan State University Extension
Extension Bulletin E-2709
September 1999
Introduction: A reliable supply of electrical power is essential.
A standby generators properly connected to essential loads can insure
reliability of the electrical supply in a manner that is safe from potential
hazards of fire or electrical shock.
Sizing a Standby Generator: List essential equipment that must
be operated during a power outage. A refrigerator or freezer will keep
food cold for a period of time if not opened. Heat the house to a comfortable
temperature then shut off the furnace while other equipment is operated.
Operating equipment on an as-need basis, the minimizes generator size.
Table 1 Typical load requirements for some common household
appliances that may need to be operated during a power outage.
- electric fan, portable 75 to 300 watts
- electric water heater 1500 to 4500 watts
- freezer 1/4 to 1/2 hp
- furnace blower 1/4 to 1/2 hp
- furnace oil burner 1/6 hp
- fluorescent and HID lights
- wattage of lamps times 1.2
- garage door opener 1/6 to 1/2 hp
- incandescent light bulbs wattage of lamps
- radio 50 watts
- refrigerator 1/4 hp
- security system minimal
- septic system pump 1/4 to 1/2 hp
- smoke detector minimal
- sump pump 1/2 to 3/4 hp
- television 200 to 600 watts
- water pump 1/2 to 2 hp
Electric motors require about four times as much power to get started
as they need to keep running. Allow 1000 Watts (1 kW) of generator capacity
for each running motor horsepower (hp). Allow four times the running
kW for motor starting.
Example: A standby generator supplies a 1/2 hp furnace blower
and a 1/3 hp sump pump. The 1/2 hp motor will require about 500 watts
for running and 2,000 watts for starting. The 1/3 hp motor will require
about 333 watts for running and 1,132 watts for starting. The generator
must be able to start the largest motor with the smaller motor running
which in this case requires a generator with a capacity of 2,333 watts
or 2.333 kW.
Sizing the Generator's Engine: Generators that are not part
of an engine/generator set must be powered with an internal combustion
engine with sufficient horsepower to run the load and start motors.
The engine should develop at least 2-1/2 hp for each kilowatt of generator
rating.
Connecting to a Standby Generator: Making the connection from
the generator to the electrical system in a safe manner is essential.
If connected improperly, the generator can be a shock hazard to occupants
of the building or to utility personnel who may be working on the electrical
distribution lines.
Generator connections must: be done in such a manner that generator
power cannot get through to the utility system prevent any terminals
from being energized when exposed, and have an ampere rating sufficient
for the load.
The standby generator must be connected in such a way that circuits
can receive power from the utility line or the generator This is accomplished
by use of a double-pole transfer switch. There are three common methods
of installing the double-pole switch.
Method 1: A double-pole transfer switch can be installed in
the electrical service entrance to a building ahead of the service panel
(Figure 1). Usually a flexible cord extends from the transfer switch
to the generator. The handle of the transfer switch is either in the
utility supply position or in the generator position. With this method
any circuit in the service panel can be operated as long as the generator
kW rating is sufficient to supply the load.


Method 2: puts the double-pole transfer switch between an adjacent
separate essential circuit panel and the main service panel (Figure
2). The essential circuit panel receives power from the utility supply
or from the standby generator. By using this method it is not necessary
to rewire the service entrance to the building. A disadvantage is that
only circuits in the essential circuit panel can receive power from
the standby generator. An essential circuit panel is available with
two interlocked circuit breakers that eliminate the need for a separate
transfer switch (Figure 2). One of the circuit breakers connects to
the main panel and the other connects to the standby generator plug.

Method 3: puts the double-pole switch on the individual circuits
(Figure 3). An approved panel containing several double-pole switches
is attached to the service panel. These panels are prewired and ready
for connection. They also contain a plug ready for connection to the
standby generator. The wire of the essential circuit is removed from
the circuit breaker and connected to the double-pole switch input wire.
The output wire from the double-pole switch is connected to the circuit
wire that was removed from the circuit breaker.
Locating the Standby Generator: The standby generator must be
located outside in a well ventilated space. Special plugs with weatherproof
enclosures can be installed on the outside of the building ready for
connection to a portable generator. If the connection plug is located
inside the building (method 3), a flexible cord is required long enough
to extend from the plug to the portable generator located outside.
The standby generator will have an output circuit protector rated in
amperes. The flexible cord leading from the generator must have an ampere
rating not less than the rating of the circuit protector on the generator
(Table 2).
Table 2 Flexible copper conductor ampere ratings.
- AWG # 10 30 amperes
- AWG # 8 40 amperes
- AWG # 6 55 amperes
- AWG # 4 70 amperes
- AWG # 2 95 amperes
Solving Problems: Some portable standby generators are intended
for use as a stand-alone system to power portable equipment and have
a ground fault circuit interrupter (GFCI) protecting the output circuit.
The purpose of this device is to sense when a person may be receiving
a shock and automatically disconnect power to the receptacle. This same
device can interfere with operation when connected to a building wiring
system.
The equipment grounding wire and the neutral wire are connected together
at the service panel in a building and inside the generator. The equipment
grounding conductor and the neutral conductor will act as parallel conductors
between the service panel and the generator. This signals a false ground
fault to the generator and the GFCI will trip. In this situation the
neutral conductor in the cord acts both as a current carrying conductor
and a safety ground.
More Information: There are publications available that provide
details on the selection, connection, and operation of standby generators.
To get started please contact your local Extension office, power supplier
customer service department.
Authors: Robert J. Fick, Ph.D., P.E., Truman C. Surbrook, Ph.D., P.E.,
Jonathan R. Althouse, Master Electrician, and Howard J. Doss, M.S.,
Agricultural Safety Specialist Agricultural Engineering Department Michigan
State University
This publication is for educational purposes only.
This publication was partially funded by the Michigan Agricultural Electric
Council (MAEC) which develops and presents educational programs on electrical
issues to agricultural professionals. The MAEC members include academic,
regulatory and industry representatives from Michigan and surrounding
states. Michigan State University is an Affirmative Action/Equal Opportunity
Institution. Michigan State University Extension programs and materials
are open to all without regard to race, color, national origin, gender,
religion, age, disability, political beliefs, sexual orientation, marital
status, or family status. Issued in furtherance of MSU extension work
in agriculture and home economics, acts of May 8 and June 30, 1914,
in cooperation with the U.S. Department of Agriculture. Arlen Leholm
extension director, Michigan State University, East Lansing, MI 48824-1039.