> Extension
& Outreach >Electrical Publications
Paper No. 983007
An ASAE Meeting Presentation
ELECTRIC FENCE SYSTEM INFLUENCE ON ANIMAL CONTACT VOLTAGE
Authors:
Robert J. Fick, Ph.D., P.E.
Agricultural Engineering Department
Michigan State University
East Lansing, MI,
USA
Truman C. Surbrook, Ph.D., P.E.
Agricultural Engineering Department
Michigan State University
East Lansing, MI, USA
Mark G., Holycross, Graduate Assistant
Agricultural Engineering Department
Michigan State University
East Lansing, MI, USA
Jonathon R. Althouse, MS
Agricultural Engineering Department
Michigan State University
East Lansing, MI, USA
Written for Presentation at the 1998 International
Meeting Sponsored by ASAE Orlando, FL, July 11 to 16, 1998
Summary: Grass contact with an electric fence can provide a
pathway for enough voltage between the fencer ground terminal and remote
earth to deliver an uncomfortable shock. The possibility of a fence
charger reaching an animal contact is reduced by improving farm grounding.
It is possible to get perceivable neutral-to-earth voltage due to a
high resistance neutral to a building with a fence charger. With a ground
rod located one meter from the fence system ground, enough voltage appeared
at the second ground to be perceived by a human. Connecting the ground
to other grounds reduced the voltage. A Fluke 87 was able to detect
fencer pulses when the pulse magnitude was large enough to be perceived,
but was not representative of the peak voltage output.
Keywords: Stray Voltage, Electric Fence, Transient Voltage,
Grounding
The authors are solely responsible for the content of this technical
presentation. The technical presentation does not necessarily reflect
the official position of ASAE, and its printing and distribution does
not constitute an endorsement of views which may be expressed. Technical
presentations are not subject to the formal peer review process by ASAE
editorial committees; therefore, they are not to be presented as refereed
publications. Quotation from this work should state that it is from
a presentation made by Fick, R.J. et al, at the 1996 Annual ASAE meeting.
EXAMPLE: Fick,R.J., et al, " ELECTRIC FENCE SYSTEM INFLUENCE ON ANIMAL
CONTACT VOLTAGE ." Presented at the 1998 International Meeting, Paper
No. 983007. ASAE, 2950 Niles Rd., St. Joseph, MI 49085-9659, USA. For
information about securing permission to reprint or reproduce a technical
presentation, please address inquires to ASAE. ASAE, 2950 Niles Rd.,
St. Joseph, MI 49085-9659, USA. Voice: 616-429-0300 FAX: 616-429-3852
E-mail:hq@asae.org
Introduction: Low impedance electric fence energizers are capable
of making contact with vegetation and still maintaining the capability
of delivering a repelling shock to livestock. The internal impedance
of the energizer is low thus allowing a large current flow to occur
for a controlled time period. The out put energy of the energizer is
a function of the output voltage and the time interval of the pulse.
Manufacturers directions for these fence energizers emphasize the importance
of establishing a good low resistance grounding system for the energizer
that is separated from the electrical system ground,or any metal equipment
with which the livestock may make contact. The energizer is nothing
more than a source of a high voltage short duration pulse of voltage
which will result in a short duration current pulse when a circuit is
completed. The wire mounted on insulators is one terminal, and the earth
is the other terminal. Current will flow when the circuit is completed
by livestock, vegetation,or equipment making contact between the wire
and the earth. A low resistance grounding electrodeis needed to complete
the circuit back to the energizer. If vegetation or an animal makes
contact with the fence, the circuit is completed and current flows to
earth and returns to the energizer by way of the grounding electrode.
Ohm's law describes the electrical condition where current flowing
over a resistance results in a voltage. If current is flowing in the
electric fence circuit, there will be a voltage developed between the
fence system ground rod and the adjacent earth during the time interval
when the current if flowing. If the current is a short duration pulse,
the voltage at the ground rod will be a short duration pulse. If this
fence system ground rod makes contact with the electrical system grounds,a
neutral-to-earth voltage pulse will be experienced at various locations
on the farm. Figure 1 shows a properly installed electric fence system
that is making contact with vegetation, and a current pulse results
every time the wire is energized. Figure 2 shows the voltage pulse from
the fence system ground rod to an adjacent point on the earth. The duration
of the pulse is a function of the energizer design. The magnitude of
the voltage at the ground rod depends upon the level of current flow
in the earth and the resistance of the grounding electrode. The higher
the grounding electrode resistance is, the higher the voltage between
the grounding electrode and the earth will be . If the energizer grounding
electrode is connected to the electrical system grounds, then the entire
farm grounding system will act as the ground return path for the fence
energizer. This will result in a voltage pulse being present at locations
throughout the farm.
Figure 1 A pulse of current will flow through the earth and return
to the energizer when vegetation, livestock, or equipment makes contact
with the electric fence.

Figure 2 A voltage pulse will occur between the fence energizer grounding
electrode and an adjacent point on the earth every time an earth current
pulse occurs.
Voltages from electric fencers are frequently reported showing up at
waterers and other animal contacts by neutral-to-earth voltage investigators,
but publications quantifying these voltages have not been found. Sheldon
(1993) looked at fencer outputs for different controllers and fence
configurations. He measured voltage at fence contacts along the length
of the fence for different fence configurations.
Gettman (1983) addressed the testing of the standards and performance
characteristics of electric fences by Underwriter Laboratories in its
Standard for Safety for Electric Fence Controllers,UL 69 (1993). If
a fence controller is found to meet the requirements specified in UL
69, and if the manufacturer agrees to subscribe to UL's Follow-Up Service,
UL can extend Listing coverage to that particular controller and authorize
the manufacturer to use the appropriate UL Registered Mark on those
controllers which meet UL's requirements. The output of the fencer must
not exceed a curve of current plotted against pulse duration. Both of
the fence controllers we tested were Unregistered. Many of the higher
powered low impedance chargers available are not UL Registered.
Objectives: Low impedance electric fence systems have been claimed
to be a source of electrical current that affected animal behavior and
possibly productivity. This research examines the operating characteristics
of a low impedance electric fence system to determine any possible way
during operation it can create a voltage between animal contact points.
Current flow was measured through a simulated animal at the contact
points using a resistor of a value comparable to that of livestock.
Specific situations examined were:
- An electric fence system grounded to the farm electrical system
grounding system with the fence making contact with grass.
- The electrical system ground or metal livestock equipment located
in close proximity to the electric fence system grounding electrode
with the fence making contact with grass.
- A high resistance neutral supplying a 120 volt electric fence system
properly installed with and without grass contact with the fence.
A commonly available digital multimeter that has been used to measure
transient voltages was also tested and compared with an oscilloscope
to determine if it can be a reliable means of predicting whether a voltage
may be present between animal contact points resulting from electric
fence operation. Human subjects also tested voltages between animal
contact points to determine if voltages by these three methods could
be perceived.
Experimental Procedure: Only low impedance fence energizers
that were listed by Underwriters' Laboratories were tested as a part
of this research. The first energizer had an output rating of 6 Joules
and was a Farmworks® Model 4400-B, and the second energizer did not
have an output energy rating and was a Parker McCrory Fieldmaster® Model
FM-1. The first step in the testing was to determine the amount of current
that would flow when the fence wire made contact with sandy soil with
a dry surface, and the current flow that would occur as the fence wire
made contact with grass. Current flow was measured with a Tektronix
TekScope® Model THS720 Std with a Tektronix ac current probe Model P6021
capable of detecting short duration current pulses. The voltage was
measured across a 550 ohm carbon resistor connected between the fence
energizer grounding terminal and are mote ground rod which had a resistance
of 25.1 ohms. Grounding electrode resistances were measured using the
three-point fall of potential method with a Biddle Megger® DET 5/2.
Human perception was determined by using a minimum of three individuals.
A glass beaker was filled with salt water and an electrode inserted
into the salt water was connected to the ground terminal of the fence
energizer. A copper cylinder 1.6 cm in diameter and 5 cm long was wetted
with salt water and grasped in the palm of the hand. The cylinder was
connected to the same ground rod as the 550 ohm resistor. While grasping
the cylinder in the palm of the hand, the index finger was inserted
into the beaker of salt later.
A Fluke Model 87 digital multimeter has been used in the field to measure
the short duration transient voltages. In the 1 ms maximum mode, the
meter records the maximum voltage value that occurs over a one millisecond
interval and averages that value with all previous maximum values recorded.
As the voltage pulse decreases in duration from 1 ms, the meter records
a value that is less than the peak voltage. This meter was used to measure
the voltage across the 550 ohm resistor and compared with the peak voltage
measured with the oscilloscope.
The electric fence wire was mounted so that a 15 meter length was
making contact with green grass. The wire was mounted 0.75 meters above
the ground. The first experiment evaluated two different energizers
with four levels of fence system grounding resistance. This was to simulate
the condition where the fence system was grounded to the farm electrical
system. The four levels of fence system ground resistance were 40.0
ohms, 25.4 ohms, 10.3 ohms, and 2.9 ohms. In addition to capturing the
wave form of the current through the 550 ohm resistor and the voltage
across the resistor, the oscilloscope determined the peak value of the
voltage and the peak value of the current. Perception was determined
by human subjects. A schematic diagram of the experiment is shown in
Figure 3.
Figure 3 A schematic diagram of the electric fence circuit in experiment
one where the fence was faulted to earth through grass and the voltage
was measured from the earth to the ground terminal of the fence energizer.
The second experiment was concerned with the flow of current in the
120 volt supply to the energizer and whether that current was of sufficient
value to cause a voltage drop on the neutral supplying the building.
If there was a high resistance in the neutral supplying the building,
a neutral-to-earth voltage pulse would occur due to the current flow
to the fence energizer. Two fence energizers were tested at three levels
of neutral resistance. Neutral resistances tested were 2.0 ohms,1.02
ohms, and 0.12 ohms. The supply end of the neutral resistance was connected
to earth through an 11.2 ohm grounding electrode and at the load end
through a 25.1 ohm grounding electrode. The fence energizer was properly
installed and grounded to a 10.3 ohm grounding electrode. The experiment
was conducted with the fence faulted to earth through grass and the
fence not faulted to earth. A schematic diagram of the experiment two
is shown in Figure 4.
Figure 4 A schematic diagram of the electric fence circuit in experiment
two where the neutral supplying the fence energizer simulating the neutral
of a feeder to the building has three different levels of conductor
resistance.
Experiment three examined the influence of a gradient near the fence
energizer grounding electrode on an adjacent ground rod. Two grounding
electrodes located one meter apart were tested with one ground rod connected
to the fence energizer with voltage measured to the other ground rod.
In the first part of the experiment that ground rod was tested by itself,
and in the second part it was connected to an 11.2 ohm grounding electrode
located several hundred feet away. The first part of the experiment
was similar to locating metal livestock equipment close to a fence energizer
grounding electrode. The electric fence was faulted to earth through
grass contact to create a voltage gradient near the fence energizer
grounding electrode. The schematic diagram of this experiment is shown
in Figure 5.
Figure 5 A schematic diagram of the electric fence circuit in experiment
three where a second ground rod was located one meter from the fence
energizer ground rod. The circuit was modified later so the ground rod
was connected to an 11.2 ohm ground.
Results and Discussion: Experiment one examined the voltage
from the fence energizer grounding electrode to earth with different
grounding resistances as shown in Figure 3. A summary of the data is
shown in
Table1. The voltages in the table are measured across a 550 ohm resistor
connected from the fence energizer ground to remote earth.
Energizer Energizer Fluke 87 Tektronix Perception
model ground 1ms peak peak peak human
ohms volts volts amps
4400 40.0 64.4 176 1.48 Pain
4400 25.4 28.4 116 0.92 Uncomfortable
4400 10.3 25.3 46 0.41 Noticeable
4400 2.9 2.4 16 0.10 Very slight
FM-1 40.0 21.2 172 1.76 Slight
FM-1 25.4 2.4 122 1.08 None
FM-1 10.3 0.1 40 0.38 None FM-1 2.9 0.1 22 0.18 None
Figure 6 Voltage from fence energizer ground to earth across a 550
ohm resistor and current through the resistor for the model 4400 fence
energizer with fence energizer grounding resistance of 25.4ohms.

Figure 7 Voltage from fence energizer ground to earth across a 550
ohm resistor and current through the resistor for the model FM-1 fence
energizer with fence energizer grounding resistance of 25.4ohms.
Figure 8 Peak voltage of the wave form for the model 4400 fence energizer
with different levels of fence energizer grounding resistance.
In experiment two the 120 volt line feeding the fence energizer was
studied to determine the influence of neutral resistance on neutral-to-earth
voltage at the building where the fence energizer is installed. The
question was whether the current flow to the fence energizer is of sufficient
magnitude to create a neutral-to-earth voltage pulse that can be perceived
by livestock in the building. Peak values of neutral current for the
model 4400 fence energizer are given in Table 2 along with the voltages
measured from the neutral in the building to the earth. The peak neutral
currents were in excess of 20 amperes when the fence energizer put a
voltage on the fence wire. It did not make a difference whether the
fence was faulted to the earth. Figure 9 shows the flow of neutral current
for the model FM-1 energizer and it can be seen that the line current
peaks at the moment voltage is applied to the fence. Figure 9 shows
the voltage drop across the resistance in the neutral supplying the
fence energizer and the peak current drawn by the fence energizer. It
can be seen by the data in Table 2 that for the FM-1 energizer the voltage
did not reach a level that would cause human perception. Figure 10 shows
the neutral current and neutral voltage drop for the model 4400 fence
energizer. In Table 2, it can be seen that a neutral-to-earth voltage
pulse could be perceived for the model 4400 energizer.
Table 2 Experiment two with resistance in the neutral conductor of
the supply to the fence energizer and the resulting voltage from the
building neutral to earth.
Energizer Fault Neutral Fluke 87 Tektronix Perception
model resistance 1ms peak peak peak neutral human
ohms volts volts amps amps
4400 Yes 2.0 5.5 11.2 ------ 24.0 Slight
4400 No 2.0 5.8 12.0 0.112 24.0 Slight
4400 Yes 1.02 2.6 8.2 0.068 23.6 Very slight
4400 No 1.02 2.8 8.2 0.080 25.2 Very slight
4400 Yes 0.12 2.5 3.8 0.048 28.0 None
4400 No 0.12 2.5 4.6 0.036 26.8 None
FM-1 Yes 2.0 1.0 0.7 0.020 0.18 None
FM-1 No 2.0 1.0 ---- ------ 0.15 None

Figure 9 The neutral current and neutral voltage drop are shown for
the model FM-1 fence energizer with 2 ohms of resistance in the neutral
supplying the energizer. The voltage and current maximums occur at the
moment voltage is applied to the wire.
Figure 10 The neutral current and neutral voltage drop are shown for
the model 4400 fence energizer with 2 ohms of resistance in the neutral
supplying the energizer. The voltage and current maximums occur at the
moment voltage is applied to the wire.
Experiment three investigated the influence of the voltage gradient
near the fence energizer grounding electrode on a ground rod located
at a distance of only one meter. This test was only conducted for the
model 4400 faulted to earth through grass. The data are shown in Table
3. For the first test the ground rod was not connected to any external
grounds. For the second test the ground rod was connected to another
grounding electrode locates several hundred feet away. For the first
test the voltage measured from the isolated ground rod to a reference
ground was sufficiently high to cause human perception. As soon as the
ground rod was connected to another ground rod the voltage dropped dramatically
to a level well below human perception. If the ground rod had been located
closer than one meter, the voltage most likely would have been higher.
This test does show that it is possible to achieve a voltage at the
perception level by locating metal objects that can be contacted very
close to the fence energizer grounding electrode.
Table 3 Experiment three with the electrical system ground rod located
one meter from the fence energizer ground rod with the fence faulting
to earth through vegetation.
Energizer Energizer Fluke 87 Tektronix Perception
model ground 1ms peak peak peak human
volts volts volts amps
ground rod isolated
4400 18.8 4+ 10.9 0.092 Slight
ground rod connected to another 11.2 ohm ground
4400 16.9 0.9 9.4 0.084 None
Examination of the data in the Tables shows that the voltage measurements
made by the Fluke 87 digital multimeter on the one millisecond maximum
setting did not accurately represent the peak voltage of the wave form.
The peak voltage for the model FM-1 and 4400 were similar for the same
conditions, but examination of Figure 2 shows that the pulse width for
the model FM-1 was much shorter than for the model 4400. As a result
the Fluke 87 multimeter yielded a lower voltage reading for the model
FM-1 than for the 4400 for approximately the same peak voltage. Comparing
the perception of the different experiments with the voltage recorded
by the Fluke 87 tells a different story. Except at very low voltages,
the Fluke 87 voltage set on the 1 ms maximum setting was a reasonable
indicator of the level of perception at least for these two fence energizers.
The subjective perception level for at least three human subjects compared
with the Fluke 87 voltage reading is summarized in Figure 11.
Figure 11 The human perception compared with the Fluke 87 voltage readings
set to record the 1millisecond maximum.
Conclusions
- Given enough weed contact with the fence, voltages between the fencer
ground terminal and remote earth will be high enough to deliver an
uncomfortable shock.
- The pulse or pulses that occurred during line charging can cause
a neutral-to -earth voltage that is high enough to be perceived.
- If a voltage is present, a Fluke 87 Multimeter can generally be
used to detect that voltage, but because pulse length affects the
reading of the meter, it is not as reliable at determining if the
voltage will be of a magnitude that will be perceived.
Acknowledgments: Support for this project was provided by the
Michigan State University Agricultural Experimentation Station and the
Michigan Agricultural Electric Council.
References: Gettman, K.E. "Standards, Performance Characteristics
and the Testing of Electric FenceControllers". Presented at the 1983
Winter International Meeting, Paper No. 834554. ASAE, 2950 Niles Rd.,
St. Joseph, MI 49085-9659, USA.
Sheldon, L. "Field Tests of Electric Fence Controllers". Presented
at the 1993 Winter International Meeting, Paper No. 933523. ASAE, 2950
Niles Rd., St. Joseph, MI 49085-9659, USA.
Underwriters Laboratory. Standard for Safety for Electric Fence Controllers,
UL 69. 1993. Underwriters Laboratory Inc., 333 Pfingsten Road, Northbrook,
IL 60062-2096. AgE M