Disconnection of the telephone grounding bond at livestock
farm pedestals
A cooperative procedure developed by:
The Michigan Agricultural Electric Council and the Telecommunications
Association of Michigan
By
Jim Schrandt
In Michigan there are dozens of electric power suppliers and telecommunications
providers. Each of these electric utilities and telephone companies
provide their respective service to livestock farms, and each had their
own installation and maintenance procedures to prevent the possibility
of the utility system from becoming a possible source of stray voltage
on the farm. Communication and coordination of these procedures were
varied and challenging. To provide a consistent procedure and improve
communication, the Michigan
Agricultural Electric Council(MAEC), based in the Department
of Biosystems & Agricultural Engineering at Michigan State University,
and the Telecommunications Association
of Michigan(TAM), teamed up to develop the following procedure.
Members of the MAEC include most of the suppliers of electric power
in Michigan, and members of the TAM include most of the suppliers of
telephone service in Michigan.
ELECTRIC UTILITY PROCEDURE:
Electric utilities frequently separate primary and secondary grounded
neutrals at the transformer serving livestock farm customers. This procedure
prevents off-site neutral-to-earth voltage from becoming a possible
source of stray voltage at animal contact locations on the associated
farm.
NORMAL TELEPHONE COMPANY OPERATING PROCEDURE:
Local telephone companies bond the buried drop shield to the main cable
shield(s). The drop shield is also bonded to the electric power ground
at the subscriber premise, as required by the National Electrical Safety
Code and the National Electrical Code. At locations where the electric
power utility has separated their primary and secondary neutrals, the
normal telephone company operating procedure may provide a path between
the electric primary and secondary neutrals. This path could allow current
from the electric power company primary neutral to be present on the
farm wiring.
When it has been established that the telephone company’s drop
shield has become the path for primary/secondary electric power neutral
voltages, the telephone company shall disconnect its bond at the serving
pedestal by way of a special procedure and equipment installation.
THE MICHIGAN AGRICULTURAL ELECTRIC COUNCIL RECOMMENDS THE FOLLOWING
COOPERATIVE PROCEDURE:
1. The local electric utility, upon determining that it will separate
primary and secondary neutrals at the electric service transformer
serving a livestock farm customer, will contact the local telephone
company to request disconnection of the lateral bonding at the pedestal.
2. The local telephone company will expeditiously consider the electric
utility’s request, and determine whether to disconnect the shield
bond at the pedestal. When the local telephone company has made a
determination, it will contact the electric utility to inform it of
its decision, and provide an estimated date and time of action it
may take. The local telephone company will also notify the electric
utility after completing action.
3. In cases where the lateral shield bond is disconnected, the telephone
company technician will install a “Notice” decal, provided
by the Michigan Agricultural Electric Council, on the outside of the
pedestal. (See Telecommunication
Grounding Decal below.) The decal will notify the technician that
the lateral shield is not bonded. The Telecommunications Association
of Michigan provided a recommended procedure to local telephone companies
for disconnection of the lateral shield bond, devised by a licensed
telecommunications engineer.
4. While accessing pedestals serving livestock farms, the telephone
company technician will verify the status of the lateral shield bonding.
If the technician finds that the lateral bond has been disconnected,
and no “Notice” decal is visible on the pedestal exterior,
he/she will apply the “Notice” decal. The technician will
also confirm that the disconnecting procedure/equipment has been done
in accordance with item 3 above.